Phase | |
---|
Capacity | 3000VA / 2700W |
---|
INPUT |
Nominal Voltage | 208 / 220 / 230 / 240 VAC |
---|
Voltage Range | 120-300 VAC (Based on load at 50%) 180-300 VAC (Based on load at 100%) |
---|
Frequency Range | 40 Hz ~ 70 Hz |
---|
Power Factor | ≥ 0.99 @ Nominal Voltage (100% load) |
---|
Input Connections | IEC 60320-C19 to BS1363A |
---|
OUTPUT |
Output Voltage | 110 / 115 / 120 / 127 VAC or 208 / 220 / 230 / 240 VAC |
---|
AC Voltage Regulation (Batt. Mode) | ±1% |
---|
Frequency Range (Synchronized Range) | 47~53 Hz or 57~63 Hz |
---|
Frequency Range (Batt. Mode) | 50 Hz or 60Hz ± 0.5 % |
---|
Current Crest Ratio | 3:01 |
---|
Harmonic Distortion | ≤ 3%THD (Linear Load) ; ≤ 6%THD (Non-linear Load) |
---|
Output Connections | (3) BS 1363A + Terminal Block |
---|
TOPOLOGY |
Transfer Time | AC Mode to Batt. Mode | 0 ms |
---|
Inverter to Bypass | 4 ms (Typical) |
---|
Waveform (Batt. Mode) | Pure Sinewave |
---|
EFFICIENCY |
AC Mode | 80% |
---|
Battery Mode | 88% |
---|
BATTERIES |
Battery Capacity | 12V 9Ah |
---|
DC Voltage | 72V |
---|
Typical Recharging Time | 4 hours recover to 90% capacity |
---|
Charging Current (Max.) | 1A |
---|
Charging Voltage | 82.1 ± VDC 1% |
---|
SYSTEM |
LCD Display | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
---|
Audible Alarm | Battery Mode | Sounding every 4 seconds |
---|
Low Battery | Sounding every seconds |
Overload | Sounding twice every seconds |
Fault | Continuously sounding |
COMMUNICATIONS / MANAGEMENT |
Smart RS-232 / USB | Supports Windows® 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10, Linux and MAC |
Intelligent Slot | SNMP / AS400 Card |
STANDARDS / APPROVALS |
Compliances | CE |
IP Rating | IP 20 |
ENVIRONMENT |
Operating Temperature | 0°C ~ 40°C |
Relative Humidity | 20-90 % (non-condensing) |
Acoustic Level at 1m | ≤ 50dB |
PHYSICAL PROPERTIES |
Dimensions (W x D x H)mm | 190 x 421 x 318 |
Net Weight (kg) | 27.6 |