Model | MX-1000EPS |
Capacity | 1000 VA / 900 Watts |
INPUT | |
Rated voltage | 208 V / 220 V / 230 V / 240 VAC + 25% |
Voltage range | 176 ~ 280 VAC (no derating); 280 ~ 300 VAC (derating 50%) |
Frequency | 40 ~ 70 Hz (auto-sense) |
Power factor | ≥ 0.99 |
Bypass voltage range | -25% ~ +15% |
OUTPUT | |
Voltage | 208 V / 220 V / 230 V / 240 VAC |
Voltage regulation | +1% |
Frequency | 45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode) |
Waveform | Sinusoidal |
Crest factor | 3:01 |
Harmonic distortion | ≤ 2% (linear load); ≤ 5% (non-linear load) |
Transfer time | Mains mode to battery mode: 0 ms |
| Inverter mode to bypass mode: 0.2 ms (typical) |
Overload capability | 105% ~ 125%: transfer to bypass in 1 min; |
| 125% ~ 150%: transfer to bypass in 30 s; |
| > 150%: transfer to bypass in 300 ms |
EFFICIENCY | |
Mains mode | ≥ 90% |
Battery mode | ≥ 85% |
ECO mode | ≥ 95% |
BATTERIES | |
DC voltage | 36 V |
Charging current (max.) | 6A |
Recharge time | 8 hours |
ALARMS | |
Utility failure | 4 s per beep |
Low battery | 1 s per beep |
Overload | 1 s twice beep |
UPS fault | Long beep |
COMMUNICATIONS | |
RS232 (standard) / USB (optional) | Supports Windows® 98 / 2000/ 2003 / XP / Vista / 2008 / Windows® 7 / 8 / 10 |
SNMP (optional) | Power management from SNMP manager and web browser |
OTHERS | |
Operating temperature | 0 ~40°C |
Relative Humidity | 0 ~ 90% (non-condensing) |
Noise level | ≤ 50 dB (1m) |
Dimensions (WxDxH) mm | 144 x 336 x 214 |
Net weight (kg) | 6 |
Gross weight (kg) | 7 |