MX-10000EP / MX-10000EPS
| |
---|
MODEL | MX-10000EP / MX-10000EPS |
Capacity | 10kVA / 9kW |
INPUT | |
Rated voltage | 360 / 380 / 400 / 415 Vac |
Voltage range | 277 ~ 485 Vac ( no downgrading ), 190 ~ 277 Vac ( linear downgrading between 50% ~ 100% load ) |
Rated frequency | 50 / 60 Hz ( auto-sensing ) |
Frequency range | 40 ~ 70 Hz |
Power factor | ≥ 0.99 |
Bypass voltage range | -40% ~ +15% ( settable ) |
Total harmonic distortion (THDi) | ≤5% |
OUTPUT | |
Rated voltage | 360 / 380 / 400 / 415 Vac |
Voltage regulation | ±1% |
Frequency | 45 ~ 55 Hz or 55 ~ 65 (synchronized range ); 50 / 60 Hz ±0.1% in ( battery mode ) |
Waveform | Sinusoidal |
Power factor | 0.9 |
Total harmonic distortion (THDv) | ≤ 2% ( linear load ); ≤ 5% ( non-linear load ) |
Crest factor | 3:1 |
Overload (Inverter) | 102% ~ 125% for 10 min, 125% ~ 150% for 1 min, >150% for 0.5 s |
Overload (Bypass) | 102% ~ 125% for 20 min, 125% ~ 150% for 2 min, >150% for 1 s |
BATTERIES | |
DC voltage | Standard model : 240 Vdc; Long time model : 192 Vdc ( 168 / 192 / 216 / 240V optional ) |
Inbuilt battery of standard model | 20 x 7 Ah |
Charging current | Long time model : 7 A supplied ( additional 7 A is optional ) Standard model : 1 A, 2 A, 3.5 A settable |
Recharge time | Standard model : 90% capacity restored in 4 hours; Long time model : depend on the capacity of battery |
SYSTEM | |
Efficiency | ≥ 93%, ECO mode 98% |
Transfer time | 0 ms |
Max. number of parallel connections | 6 |
Protections | Short-circuit, overload, overtemperature, excessive low battery, overvoltage, undervoltage, fans failure |
Communications | RS232 / USB ( standard ), RS485 / dry contacts / SNMP ( optional ) |
Display | LCD + LED |
Standards | EN 62040-1, EN 62040-2, EN 61000-3-12, EN 61000-3-2, EN 61000-3-11, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2 |
OTHERS | |
Operating temperature | 0℃ ~ 40℃ |
Storage temperature | -25℃ ~ 55℃ ( without battery ) |
Relative humidity | 0% ~ 95% ( non-condensing ) |
Altitude | ≤ 1000m; derating 1% for each additional 100m |
IP rating | IP 20 |
Noise level at 1 m | ≤ 60 dB |
Online thermal dissipation | 3504 BTU / hr |
Dimensions ( W x D x H ) (mm) | 350 x 655 x 732 (S) |
| 350 x 785 x 858 |
Packaged dimensions ( W x D x H ) (mm) | 472 x 780 x 920 (S) |
| 472 x 910 x 1050 |
Net weight (kg) | 55 (S), 115 |
Gross weight (kg) | 65 (S), 125 |
MX-20000EP / MX-20000EPS
| |
---|
MODEL | MX-20000EP / MX-20000EPS |
Capacity | 20kVA / 18kW |
INPUT | |
Rated voltage | 360 / 380 / 400 / 415 Vac |
Voltage range | 277 ~ 485 Vac ( no downgrading ), 190 ~ 277 Vac ( linear downgrading between 50% ~ 100% load ) |
Rated frequency | 50 / 60 Hz ( auto-sensing ) |
Frequency range | 40 ~ 70 Hz |
Power factor | ≥ 0.99 |
Bypass voltage range | -40% ~ +15% ( settable ) |
Total harmonic distortion (THDi) | ≤5% |
OUTPUT | |
Rated voltage | 360 / 380 / 400 / 415 Vac |
Voltage regulation | ±1% |
Frequency | 45 ~ 55 Hz or 55 ~ 65 (synchronized range ); 50 / 60 Hz ±0.1% in ( battery mode ) |
Waveform | Sinusoidal |
Power factor | 0.9 |
Total harmonic distortion (THDv) | ≤ 2% ( linear load ); ≤ 5% ( non-linear load ) |
Crest factor | 3:1 |
Overload (Inverter) | 102% ~ 125% for 10 min, 125% ~ 150% for 1 min, >150% for 0.5 s |
Overload (Bypass) | 102% ~ 125% for 20 min, 125% ~ 150% for 2 min, >150% for 1 s |
BATTERIES | |
DC voltage | Standard model : 240 Vdc; Long time model : 192 Vdc ( 168 / 192 / 216 / 240V optional ) |
Inbuilt battery of standard model | 40 x 9 Ah |
Charging current | Long time model : 7 A supplied ( additional 7 A is optional ) Standard model : 1 A, 2 A, 3.5 A settable |
Recharge time | Standard model : 90% capacity restored in 4 hours; Long time model : depend on the capacity of battery |
SYSTEM | |
Efficiency | ≥ 93%, ECO mode 98% |
Transfer time | 0 ms |
Max. number of parallel connections | 6 |
Protections | Short-circuit, overload, overtemperature, excessive low battery, overvoltage, undervoltage, fans failure |
Communications | RS232 / USB ( standard ), RS485 / dry contacts / SNMP ( optional ) |
Display | LCD + LED |
Standards | EN 62040-1, EN 62040-2, EN 61000-3-12, EN 61000-3-2, EN 61000-3-11, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2 |
OTHERS | |
Operating temperature | 0℃ ~ 40℃ |
Storage temperature | -25℃ ~ 55℃ ( without battery ) |
Relative humidity | 0% ~ 95% ( non-condensing ) |
Altitude | ≤ 1000m; derating 1% for each additional 100m |
IP rating | IP 20 |
Noise level at 1 m | ≤ 65 dB |
Online thermal dissipation | 8281 BTU / hr |
Dimensions ( W x D x H ) (mm) | 350 x 655 x 732 (S) |
| 350 x 785 x 1078 |
Packaged dimensions ( W x D x H ) (mm) | 472 x 780 x 920 (S) |
| 472 x 910 x 1260 |
Net weight (kg) | 61 (S), 175 |
Gross weight (kg) | 71 (S), 190 |
MX-30000EP / MX-30000EPS
| |
---|
MODEL | MX-30000EP / MX-30000EPS |
Capacity | 30kVA / 27kW |
INPUT | |
Rated voltage | 360 / 380 / 400 / 415 Vac |
Voltage range | 277 ~ 485 Vac ( no downgrading ), 190 ~ 277 Vac ( linear downgrading between 50% ~ 100% load ) |
Rated frequency | 50 / 60 Hz ( auto-sensing ) |
Frequency range | 40 ~ 70 Hz |
Power factor | ≥ 0.99 |
Bypass voltage range | -40% ~ +15% ( settable ) |
Total harmonic distortion (THDi) | ≤5% |
OUTPUT | |
Rated voltage | 360 / 380 / 400 / 415 Vac |
Voltage regulation | ±1% |
Frequency | 45 ~ 55 Hz or 55 ~ 65 (synchronized range ); 50 / 60 Hz ±0.1% in ( battery mode ) |
Waveform | Sinusoidal |
Power factor | 0.9 |
Total harmonic distortion (THDv) | ≤ 2% ( linear load ); ≤ 5% ( non-linear load ) |
Crest factor | 3:1 |
Overload (Inverter) | 102% ~ 125% for 10 min, 125% ~ 150% for 1 min, >150% for 0.5 s |
Overload (Bypass) | 102% ~ 125% for 20 min, 125% ~ 150% for 2 min, >150% for 1 s |
BATTERIES | |
DC voltage | Standard model : 240 Vdc; Long time model : 192 Vdc ( 168 / 192 / 216 / 240V optional ) |
Inbuilt battery of standard model | 60 x 9 Ah |
Charging current | Long time model : 7 A supplied ( additional 7 A is optional ) Standard model : 1 A, 2 A, 3.5 A settable |
Recharge time | Standard model : 90% capacity restored in 4 hours; Long time model : depend on the capacity of battery |
SYSTEM | |
Efficiency | ≥ 93%, ECO mode 98% |
Transfer time | 0 ms |
Max. number of parallel connections | 6 |
Protections | Short-circuit, overload, overtemperature, excessive low battery, overvoltage, undervoltage, fans failure |
Communications | RS232 / USB ( standard ), RS485 / dry contacts / SNMP ( optional ) |
Display | LCD + LED |
Standards | EN 62040-1, EN 62040-2, EN 61000-3-12, EN 61000-3-2, EN 61000-3-11, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2 |
OTHERS | |
Operating temperature | 0℃ ~ 40℃ |
Storage temperature | -25℃ ~ 55℃ ( without battery ) |
Relative humidity | 0% ~ 95% ( non-condensing ) |
Altitude | ≤ 1000m; derating 1% for each additional 100m |
IP rating | IP 20 |
Noise level at 1 m | ≤ 65 dB |
Online thermal dissipation | 9929 BTU / hr |
Dimensions ( W x D x H ) (mm) | 350 x 655 x 732 (S) |
| 350 x 785 x 1078 |
Packaged dimensions ( W x D x H ) (mm) | 472 x 780 x 920 (S) |
| 472 x 910 x 1260 |
Net weight (kg) | 65 (S), 235 |